Loader

Thermogard HT

Description

Thermogard HT is an environmentally friendly anticorrosive concentrate for heating and cooling systems. It is used if metallic materials are to be protected from corrosion and frost protection is not necessary.

It is free of nitrites, phosphates, amines, silicates, borates and heavy metals.

hermogard HT is biodegradable and environmentally friendly.

The heat transferability and the viscosity of the water are not influenced by Thermogard HT.

Thermogard HT Korrosionsschutzkonzentrat

Typical areas of application

Thermogard HT is e.g. used for heating systems which are subject to oxygenation despite their closed design (e.g. due to permeable plastics or sealing materials).

Packaging sizes

  • 25 kg / 30 kg PE canister
  • 220 kg Barrel
  • 1.000 kg IBC
  • 24.000 kg Tank vehicle

Specification

The thermodynamic properties and other specific product features available to download in PDF format.

Application

Thermogard HT is delivered in liquid form and can therefore be easily dissolved in water.

The applied concentration is 4% (4% Thermogard HT + 96% water).

Corrosion protection

Thermogard HT contains a complex combination of corrosion inhibitors which optimally protect metals from corrosion. This corrosive protection can be used for all important metals which are generally used for the construction of heating and cooling systems and industrial plants. Installations made of copper, brass, solder, grey iron, aluminium, steel and iron are optimally protected from corrosion, even if they are used in multi-metal installations. Plastics and sealing materials are resistant to Thermogard HT.

Application guidelines

The water which is used for the production of the solution should have a maximum hardness of 25 °dH and a chloride content of 100 mg/l maximum. Generally, tap water fulfils these requirements. Galvanised components are to be avoided, especially at higher operating temperatures. When installing the plant, it is to be ensured that the future operation is not interrupted by circulatory disturbances caused by air cushions or debris. The plants that are operated with Thermogard HT are to be installed as closed systems and are to be filled completely and vented directly after the pressure test is carried out. Gas and air cushions are to be removed immediately. Breathers are to be applied in such a way that they constantly keep the system free from air and oxygen and no air can be sucked in in case of low pressure. If an existing plant is to be filled, the corrosion condition should be checked first. Before a system that is damaged by corrosion is filled, it is to be reconstructed completely.

Other information

Thermogard HT is only used in systems which do not require any frost protection. For areas liable to frost, Glysofor is used.

Chemical name Combination of corrosion inhibitors, dissolved
Appearance Yellowish liquid
Packaging Canisters / barrels / IBCs / tank vehicles
ADR KI 0 Ziff
WHC 1
Labelling omitted
Applied concentration 4% in water
Operating temperature range +5 to +95 °C
Application areas Heating systems, cooling systems, air conditioners, biogas plants, block heating stations, heat recovery plants, industrial and production plants, anticorrosives in water and heating circuits, anticorrosives in the area of geothermal energy if no frost protection is required.
Density (20 °C) 1,14 g/cm3
pH-value 8,1 to 8,5
Boiling point (1013 mbar) from 100 °C

Any questions?

Our products are used in heating systems, air conditioners, industrial and cooling plants, heating pumps, solar plants, sprinkler systems and other systems which carry liquids.
We advise you free of charge and without obligation, so that you receive the best product for your application.